This email address is being protected from spambots. You need JavaScript enabled to view it.
radius(021) 2128 7964    hioki indonesia 0821 2198 5207                                                                insulation tester hioki Senin-Jumat: 09.00-18.00

Partial Discharge Detection Kit

Download PDetector PDF

PDetector

jual harga partial discharge pmdt pdetector

PDetector is the ideal partner for condition-based maintenance programs. Online partial discharge testing is a method of inspecting the insulation of electric power systems while equipment remains energized and in service. PDetector incorporates all 5 types of online PD sensor technology. Information from multiple sensors gives PDetector the versatility to detect all types of PD in all types of substation apparatus. Furthermore, the exact type of PD activity can be determined using PRPS: void, corona, surface, particle, or floating electrode. 

Applications:

  • Power Cables 

  • Transformers

  • GIS

  • Switchgear

  • Substation Apparatus

Sensor Technology : Detection Bandwidth 

Electromagnetic (EM)

  • TEV - Transient Earth Voltage  (built-in to main handheld unit) 3MHz - 100MHz

  • UHF - Ultra High Frequency  - 300MHz - 1.5GHz

  • HFCT - High Frequency Current Transformer 500kHz - 50MHz 

Acoustic Sensors (AE)

  • Acoustic Contact - 20kHz- 300kHz 

  • Airborne Ultrasonic - 40kHz 

Phase Resolved Partial Discharge (PRPD) - PD activity produces both electromagnetic and acoustic emissions.  PRPD mode will automatically relate the occurrence of the incoming signals to the power frequency 60Hz (or 50Hz). This gives the user the ability to instantly determine if PD is present

pdetector partial discharge pmdt

pdetector partial discharge

jual harga pdetector partial discharge pmdt

pmdt pdetector partial discharge

Software -Data Managment

PC Software is included. Enables you to build a network tree which includes all of the assets which are periodically tested.  Each test file is stored and trended.

  • Intelligent PD Recognition Software

  • Trending - Programmable warnings and alarms

  • CSV Data Export to other asset management software

  • RFID - Radio Frequency Identification - Small RFID tags

  • can be used to automatically associate test data with specific assets. Automated Data Entry

  • Intelligent Patrol - Engineers can create a procedure with all test points in a list. The test point is selected on the list and the measurement data is stored and associate with the test point. 

  • Create reports in JPEG, Excel, or MS Word. 

software pdetector partial discharge pmdt

PD asset management capabilities: allows you to RFID tag all your electrical assets. The RFID tag (Radio Frequency Identification) can be attached to your specific MV and HV electrical assets and then use our Intelligent Patrol methodology.

This feature and method allows Predictive Maintenance information such as Asset ID #, substation name, and electrical asset name, current and historical Insulation condition values to be electronically scanned, stored and saved. It provides a new test number each time a new test is conducted on the electrical asset, produces reports and data sheets as well as housing this information on a windows based platform.